PLCOPEN-L13: FOR loop variable should not be used outside the FOR loop

Referencing a FOR loop control variable after END_FOR relies on implementation-defined behavior.

Why is it bad?

The IEC 61131-3 standard does not guarantee the value of a FOR loop's control variable after the loop terminates. Different PLC runtimes may leave the variable at the last incremented value, at the bound, or at an undefined value entirely. Code that reads the variable after END_FOR is therefore non-portable and its behavior may silently change when switching vendors or runtime versions.

If you need to know where the loop stopped (e.g. after an EXIT), copy the value to a separate variable inside the loop body before exiting.

Example

PROGRAM program0
VAR
i : INT;
WORDS : ARRAY[0..100] OF STRING;
value : STRING;
END_VAR

FOR i := 0 TO 100 BY 2 DO
IF WORDS[i] = 'Key' THEN EXIT; END_IF;
END_FOR;

IF i <= 100 THEN (* PLCOPEN-L13 — i used outside FOR *)
WORDS[i + 1] := value;
END_IF;
END_PROGRAM

Use instead:

PROGRAM program0
VAR
i : INT;
found_idx : INT := -1;
WORDS : ARRAY[0..100] OF STRING;
value : STRING;
END_VAR

FOR i := 0 TO 100 BY 2 DO
IF WORDS[i] = 'Key' THEN
found_idx := i;
EXIT;
END_IF;
END_FOR;

IF found_idx >= 0 THEN
WORDS[found_idx + 1] := value;
END_IF;
END_PROGRAM

Resources

  1. PLCOpen Software Construction Guidelines